Cold Room Quotation: 7 Details to Send Your Supplier
A cold room quotation should state the operating conditions the supplier used to select the refrigeration equipment. A “5-ton freezer room” describes how much product you want to store. It does not specify the cooling capacity the system must deliver. For example, holding five tonnes of already frozen seafood and freezing fresh seafood on site impose different refrigeration loads.
The ASHRAE Handbook—Refrigeration, Chapter 24 groups refrigerated-facility loads into heat transfer through the enclosure, product cooling, internal heat sources, air infiltration, and equipment-related heat. Use the checklist below to give suppliers a common basis for their calculations and quotations.
1. State the maximum stock and peak product intake
Give maximum stock in kg or tonnes and peak intake in kg per day or kg per batch. Specify the product, packaging, and incoming product temperature. If the system must freeze unfrozen goods, state the required batch size and time allowed.
2. Separate room temperature from product temperature
Give the target room air temperature and, if the operation involves cooling or freezing incoming goods, the required final product temperature and time to reach it. Indicate whether the room is for chilled storage, frozen holding, or active cooling or freezing.
3. Provide a layout and insulation requirements
Share the usable internal dimensions, door sizes and positions, racking, aisles, and available installation clearances. Ask the supplier to state the proposed panel core and thickness, door specification, and whether floor insulation is included. Ask what enclosure assumptions were used for the heat-load calculation.
4. Describe the site and operating schedule
Give the installation city, indoor or outdoor equipment location, and expected peak door traffic. Include door opening duration, staffing, lighting, and operating hours where known. Ask the supplier to state the ambient design condition and the door-use assumptions used in the quote.
5. Confirm power supply and equipment ratings
Provide site voltage, phase, and frequency. Request the proposed condensing unit and evaporator model numbers, rated refrigeration capacity in kW at the stated selection conditions, and electrical input or current. Ask the supplier to show the evaporating condition and the relevant ambient or condensing condition alongside the capacity. Cooling capacity and electrical input measure different quantities.
6. Ask for the heat-load basis and itemized scope
Request a load summary in kW that lists the main assumptions, the calculated load, any design allowance, and the selected equipment capacity. Ask for separate lines for panels, doors, refrigeration equipment, controls, and accessories. Confirm who supplies piping, cabling, floor work, installation, and commissioning. Ask when the warranty begins and what it covers.
7. Put packing, delivery, and exclusions in writing
Ask for the lead time, packing dimensions and weights, the quoted trade term and named place or port, and a list of excluded costs. Compare prices using the same supply scope and delivery basis.
Example: a 5-tonne seafood freezer room
If five tonnes refers to maximum stock, state that explicitly. Then tell the supplier whether seafood arrives already frozen or needs to be frozen on site. In the latter case, add the largest batch, incoming temperature, required final product temperature, and time allowed. Ask both suppliers to quote against those same conditions before comparing unit sizes or prices.
Copy this brief for your supplier
Product and packaging: ___ · Maximum stock: ___ kg · Peak intake: ___ kg/day or kg/batch · Incoming product temperature: ___ °C · Room setpoint: ___ °C · Final product temperature and time allowed, if applicable: ___ · Internal dimensions: ___ · Site and door traffic: ___ · Power supply: ___ · Delivery term and named place: ___
Explore our cold room project solutions or send your project brief to Xueyun Cold Chain to discuss the equipment scope.